AC
Input Supply |
| Nominal
Voltage |
208V
- 600V, nominal +6%, -14% steady state |
| Nominal
Frequency |
50 Hz
or 60 Hz, nominal ± 5% |
| Number
of Phases |
3 phases
3 wire or 3 phase 4 wire (4 wire used to mitigate
unbalanced non-linear loads with high neutral current returns) |
| Current
Transformers |
2000:1A
supplied loose |
| |
Technical
Specifications |
| Harmonic
Current |
Global
orders 2 to 51st or specified harmonic compensation |
| Initialization
Time |
6 seconds
maximum |
| Response
Time |
100
micro-seconds |
| Current
Limited |
100%
or rating, regardless of the magnitude of harmonic current demanded
by the load |
Peak
Harmonic current |
3
x peak instantaneous |
Interrupting
Capacity |
200kA,
fused |
MTBF |
10.8
years |
Improvement
of Power Factor Correction |
Yes |
Transient
current suppression |
Yes |
Rapid
Load Variation |
Yes |
Parallel
Configuration |
Yes |
| |
User
Interface |
| Control
& Indication Panel |
Switch |
-
On-Off / Reset |
| |
Indicators |
-
Power Applied |
| |
|
-
Operate |
| |
|
-
At Max Capacity |
| |
|
-
Fault |
| |
|
-
Temp. Warning |
| |
Environmental
Conditions |
| Operating
Temperature |
0 to
40°C continuous |
| Storage
Temperature |
-30°C
to +65°C |
| Relative
Humidity |
up to
95%, non-condensing |
| Operating
Altitude |
up to
1500 m |
| |
Harmonic
Standards |
| Harmonic
Limits |
IEEE
519 (1992) UK: ER G5/4 |
| General
Guide on Harmonic, Interharmonic Measurements and Instrumentation |
EN 1000-427 (1994), IEC1000-3-4 |
| |
|
Reference
Standards |
| European
Union requirements for Power Assemblies |
EN 50178 |
| European
Union requirements for Low Voltage Assemblies |
EN 60439 |
| Vibration
Standard |
ICBO
Building Code, Section 16, Seismic Zone 4 |
Surge
Withstand Capability |
IEC
61643-1, UL 1449-2, without damage |
Transient |
IEEE
587 Class B |
| Protection |
IP20
rated enclosure (standard)
Other ingress of protection on request |
| |
Electromagnetic
Compatibility (EMC) |
| Conducted
and Radiated Emission |
EN 55011 |
Electrostatic
Discharge |
IEC61000-4-2 |
| Radiated
Immunity |
IEC61000-4-3 |
| Electrical
Past Transient |
IEC61000-4-4 |
Surge |
IEC61000-4-5 |
Power
Frequency Field Immunity Tests |
IEC61000-4-8 |
| Pulse
Magneting Field Immunity Tests |
IEC61000-4-9 |
Damped
oscillatory Field Immunity Tests |
IEC61000-4-10 |
Approvals |
IEC,
BS, UL, cUL, CSA |
|
|
| |