TECHNICAL SPECIFICATIONS 1 I 2 I 3 MECHANICAL SPECIFICATIONS AIM Size Type Approx. Weight (Kg) Dimensions H x W x D (mm) 25 Amp Chassis 50 788 x 407 x 313 Wall Mounted 59 788 x 407 x 338 50 Amp Chassis 79 1220 x 407 312 Wall Mounted 86 1220 x 407 338 100 Amp Chassis 170 1473 x 500 x 381 Floor Mounted 272 2109 x 610 x 508 150 Amp Chassis 190 1473 x 699 x 381 Floor Mounted 318 2109 x 813 x 508 200 Amp Chassis 204 1473 x 1106 x 381 Floor Mounted 397 2109 x 1220 x 508 300 Amp Chassis 250 1897 x 1106 x 381 Floor Mounted 443 2109 x 1220 x 508 400 Amp Chassis 295 1897 x 1106 x 381 Floor Mounted 489 2109 x 1220 x 508 AIR FLOW REQUIREMENT AIM Size Heat Rejection Minimum Air Flow Cubic Feet per minute Minimum Air Flow Cubic Metre per minute BTU / hr KW 25 Amp 2,049 0.6 125cfm 3.5cmm 50 Amp 3,757 1.1 250cfm 7cmm 100 Amp 7,513 2.2 250cfm 7cmm 150 Amp 11,270 3.3 375cfm 10.5cmm 200 Amp 15,026 4.4 500cfm 14cmm 300 Amp 22,500 6.6 1,140cfm 31.92cmm 400 Amp 30,000 8.8 1,520cfm 42.56cmm Go to top
MECHANICAL SPECIFICATIONS
AIM Size
Type
Approx. Weight (Kg)
Dimensions H x W x D (mm)
AIR FLOW REQUIREMENT
Heat Rejection
Minimum Air Flow Cubic Feet per minute
Minimum Air Flow Cubic Metre per minute
Go to top