Home   I    Company Info   I   Contact Us   I   Site Map

 

TECHNICAL SPECIFICATIONS

1 I 2 I 3  

MECHANICAL SPECIFICATIONS

AIM Size 

Type

Approx. Weight
(Kg)

Dimensions
H x W x D
(mm)

25 Amp Chassis 50 788 x 407 x 313
Wall Mounted 59 788 x 407 x 338
50 Amp Chassis 79 1220 x 407 312
Wall Mounted 86 1220 x 407 338
100 Amp Chassis 170 1473 x 500 x 381
Floor Mounted 272 2109 x 610 x 508
150 Amp Chassis 190 1473 x 699 x 381
Floor Mounted 318 2109 x 813 x 508
200 Amp Chassis 204 1473 x 1106 x 381
Floor Mounted 397 2109 x 1220 x 508
300 Amp Chassis 250 1897 x 1106 x 381
Floor Mounted 443 2109 x 1220 x 508
400 Amp Chassis 295 1897 x 1106 x 381
Floor Mounted 489 2109 x 1220 x 508


AIR FLOW REQUIREMENT

AIM Size 

Heat Rejection

Minimum Air Flow
Cubic Feet per minute

 

Minimum Air Flow
Cubic Metre per minute

BTU / hr KW
25 Amp
2,049
0.6
125cfm
3.5cmm
50 Amp
3,757
1.1
250cfm
7cmm
100 Amp
7,513
2.2
250cfm
7cmm
150 Amp
11,270
3.3
375cfm
10.5cmm
200 Amp
15,026
4.4
500cfm
14cmm
300 Amp
22,500
6.6
1,140cfm
31.92cmm
400 Amp
30,000
8.8
1,520cfm
42.56cmm

 