TECHNICAL DATA 3Phase, 3Wire Models at Voltage 380-415V,
50Hz
Model Number
Type
*
Connection
Harmonic Cancellation Phase Current
Arms
Corrective Reactive Current Arms
Total Current Injected Arms
Corrective VAR's
Losses @ Rated Output kW
3A025F5ACHXF
C
3P 3W
25
14
29
9.3
0.6
3A025F5AE3MF
W
3A050F5ACHXF
C
50
27
57
19
1.1
3A050F5AE3MF
W
3A100F5ACHXF
C
100
54
114
37
2.2
3A100F5AE2MF
F
3A150F5ACHXF
C
150
81
170
56
3.3
3A150F5AE2MF
F
3A200F5ACHXF
C
200
104
225
72
4.4
3A200F5AE2MF
F
3A300F5ACHXF
C
300
162
342
112
6.6
3A300F5AE2MF
F
3A400F5ACHXF
C
400
216
456
150
8.8
3A400F5AE2MF
F
TECHNICAL DATA for 3Phase, 4Wire Models at Voltage
380-415V, 50Hz
Model Number
Type
*
Connection
Harmonic Cancellation Phase Current
Arms
Corrective Reactive Current Arms
Harmonic Cancellation Neutral Current
Arms
Corrective VAR's
Losses @ Rated Output kW
4A025F5ACHXF
C
3P 4W
25
14
75
9.3
0.6
4A025F5AE3MF
W
4A050F5ACHXF
C
50
27
150
19
1.1
4A050F5AE3MF
W
4A100F5ACHXF
C
100
54
300
37
2.2
4A100F5AE2MF
F
4A150F5ACHXF
C
150
81
450
56
3.3
4A150F5AE2MF
F
4A200F5ACHXF
C
200
104
600
72
4.4
4A200F5AE2MF
F
* Type Code: C = Chassis / W = Wall Mounted / F = Floor Mounted
Notes:
Higher ratings are achieved by paralleling AIM's.
For other voltages up to a maximum of 600V please refer to sales
office.
Chassis units have control and indication panel plus two (three
for 4Wire) 2000:1A current transformers supplied loose (ring type).
Floor and Wall Mounted mounted models have high speed fuses, door
mtg. control and indication panel, cooling fan, Supply Isolation Device
fitted and CT's supplied loose.
TECHNICAL DATA for Series 3A & 4A AIM Active Harmonic Filters
HARMONIC CURRENT
ATTENUATION FACTOR (AIM OPERATING)